MODEL |
SWR |
|
POWER |
10,5 kVA ~ 2000 kVA |
|
INPUT |
|
VOLTAGE |
3x380 VAC, 3 Phase + Neutral |
|
TOLERANCE |
A) 275-450 VAC Standard, B) 310-425VAC, C) 220-400VAC, D) 310-470VAC, E) Special |
|
FREQUENCY |
50 Hz +/- %10 |
|
OUTPUT |
|
VOLTAGE |
3x380 VAC, 3 Phase + Neutral |
|
TOLERANCE |
% 2,5 Standard |
|
OVERLOAD CAPACITY |
%150 Load 10 min., %200 Load 10 Sec |
|
FREQUENCY |
50 Hz +/- %10 |
|
INDICATORS |
|
TYPE |
3 Pieces 72x72 Digital Voltmeter ( For R,S,T Phase ) |
|
MEASUREMENT |
Output Voltage |
|
PROTECTION |
|
OUTPUT VOLTAGE |
Low: 180V High: 240V |
|
GROUND LEAKAGE |
Optional |
|
OVERLOAD |
Fuse |
|
OVERHEATED |
Variac and booster transformator temperature control |
|
BY-PASS |
Standard Manuel |
|
NOISE FILTERING |
Surge Suppressor, EMI / RFI Filter |
|
GENERAL |
|
EFFICIENCY |
>= %97 ( Full Load ) |
|
REGULATION SPEED |
80V/Sec |
|
NOISE LEVEL |
< 45 dBA |
|
OP.TEMPERATURE |
0C ~ 40C, %20 |
|
HUMIDUTY |
%90 ( Non Condensing ) |
|
STORAGE TEMPERATURE |
-20C ~ +70C |
|
PROTECTION CLASS |
X-TYPE : IP20 ( Standard ), Y-TYPE IP23, Z-TYPE : IP54 |
|
COLOR |
RAL7035 |
|
COOLING |
Natural Air Cooling / Forced Cooling Width Faz |